Hello, welcome to Shenzhen Taigang Machinery Co., Ltd.!
Business:0769-81698040 13509666635 Technical Support:13509650331
English
2013-10-01 00:00:00
Click:
Regenerative dryers Maintenance Guide
Daily maintenance content :
1 day class on a pre-filter before checking the automatic drain valve.
2 Check for tower, regeneration and boost the movement is normal .
3 Check the operating conditions , inlet pressure , inlet temperature and air flow .
4 Check the moisture indicator , dried blue , pink represents humid.
5 Check whether the muffler fouling , regeneration tower represents excessive pressure back to red muffler need of replacement.
6 Check the pre-filter and post- filter pressure drop , if the pressure drop exceeds 0.5bar, replace the filter .
Back to top
Monthly maintenance content :
1 Check the heat and there is no heat regeneration dryer control air passing through the filter . Replace if necessary.
2 Check the blower dryer oriented filters filter, replace if necessary .
3 Check the blower dryer suction filter , replace if necessary .
Back to top
Quarterly maintenance content :
1 Check the front and rear filter, check the blockage and possible damage, replace as needed .
2 purge valve with compressed air .
3 Check the output state of the dew point .
Back to top
Annual maintenance content :
1 Close the connection dryer inlet / outlet as valves fully open bypass pipe , completely buck the dryer system , open the desiccant filling mouth, sampling inspection desiccant, desiccant by oil pollution and if crushed , replace desiccant.
(2) Remove and inspect the outlet check valve . Repair and replacement according to the situation .
3 Remove and inspect imported pneumatic valve and the exhaust valve regeneration , cleaning and replacing worn seats and seals.
4 Check for leaks or pneumatic valve cylinder seals for wear .
5 . Maintenance checks boost valves.
6 . Maintenance check control gas solenoid valve.
7 Calibration dew point probe ( if equipped with a dew point meter ) .
8 Check the muffler is clogged by oil or dust , back pressure than 0.35bar should be replaced.
Back to top
Note:
Maintenance on the dryer , please carefully read the instruction manual random